APPLICATION

 CJT1 series AC contactors is mainly used for remove frequently making and breaking circuit in the power system of AC 50Hz/60Hz, rated voltage to 380V,current to 150A,And it can be formed motor stater with thermal relay or electron protective device for protecting from overload circuit.
The product accords with such standards as IEC60947-4-1
、GB14048.4、JB/T8730.It's CJ10 upgrade replacement product. 

SPECIFICATIONS 

Type

CJT1-10

CJT1-20

CJT1-40

CJT1-60

CJT1-100

CJT1-150

Rated insulation voltage 
& working current

380

380

380

380

380

380

(AC-1~AC-4,380V)(V)
Rated operating current

10

20

40

60

100

150

AC-3
Rated control power

220V

2.2

5.8

11

17

28

43

380V

4

10

20

30

50

75

Per hour cycle of operation

AC-1 AC-3 600,AC-2 AC-4 300CJT1-150 AC-4 120

×106electric endurance

AC-3

60

60

60

60

60

60

AC-4

2

2

2

1

1

0.6

106Mechanical endurance

300

300

300

300

300

300

Auxiliary contact

2NO+NC,AC-15 180V;DC-13 60W 1th:5A

Fuses allocation

RT16-20

RT16-50

RT16-80

RT16-160

RT16-250

RT16-315


Coil power consumption

Starting power

65

140

230

485

760

950

Maintain power

11

22

32

95

105

110